Technology Transitions HFC Restrictions by Sector
Beginning January 1, 2025, certain technologies may no longer use high global warming potential (GWP) hydrofluorocarbons (HFCs) or HFC blends. Prohibitions apply to the manufacture, distribution, sale, installation, import, and export of products containing restricted HFCs and on the installation of new systems that use restricted HFCs. More information on the sectors and subsectors, regulatory context, and ongoing rulemakings is available on the Technology Transitions Program website.
- Aerosols – Restricted Products by Sector and Subsector Table
- Foams – Restricted Products by Sector and Subsector Table
- Self-contained Refrigeration, Air Conditioning, and Heat Pumps – Restricted Products by Sector and Subsector Table
- Refrigeration, Air Conditioning, and Heat Pumps – Restricted Systems by Sector and Subsector Table
More information
- Final Rule Fact Sheet: Restrictions on the Use of HFCs in Certain Sectors (PDF) – Find tables of restricted products for all sectors and subsectors
Aerosols – Restricted Products by Sector and Subsector Table*
Subsector | Global Warming Potential Limit or Prohibited Substances | Manufacture and Import Compliance Date1 |
---|---|---|
Consumer aerosol products | 150 | January 1, 2025 |
Technical aerosol products2 | 150 | January 1, 2028 |
Foams – Restricted Products by Sector and Subsector Table*
Subsector | Global Warming Potential Limit or Prohibited Substances | Manufacture and Import Compliance Date1 |
---|---|---|
Polyurethane3 (rigid, flexible, integral skin, laminated boardstock) | 150 | January 1, 2025 |
Polystyrene extruded boardstock and billet and extruded sheet | 150 | January 1, 2025 |
Phenolic insulation board and bunstock | 150 | January 1, 2025 |
Polyisocyanurate laminated boardstock | 150 | January 1, 2025 |
Polyolefin | 150 | January 1, 2025 |
Self-contained Refrigeration, Air Conditioning, and Heat Pumps – Restricted Products by Sector and Subsector Table*
Sort by
Subsector | Product | Global Warming Potential Limit or Prohibited Substances | Manufacture and Import Compliance Date1 |
---|---|---|---|
aStationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning) | Stationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning) | 700 | January 1, 2025 |
bResidential dehumidifiers | Residential dehumidifiers | 700 | January 1, 2025 |
cHousehold refrigerators and freezers | Household refrigerators and freezers | 150 | January 1, 2025 |
dVending machines | Vending machines | 150 | January 1, 2025 |
eMotor vehicle air conditioning | Light-duty passenger vehicles | 150 | Model Year 2025, and no earlier than [One year after date of publication in the Federal Register] |
fMotor vehicle air conditioning | Medium-duty passenger vehicles, heavy-duty pick-up trucks, complete heavy-duty vans | 150 | Model Year 2028 |
gMotor vehicle air conditioning | Listed nonroad vehicles (agricultural tractors greater than 40 horsepower; self-propelled agricultural machinery; compact equipment; construction, forestry, and mining equipment; and commercial utility vehicles) | 150 | January 1, 2028 |
hChillers (as a stand-alone product) | Industrial process refrigeration with exiting fluid below -50 °C (-58 °F) | Not covered | Not covered |
iChillers (as a stand-alone product) | Industrial process refrigeration with exiting fluid greater than or equal to -50 °C (-58 °F) and less than -30 °C (-22 °F) | 700 | January 1, 2028 |
jChillers (as a stand-alone product) | Industrial process refrigeration with exiting fluid equal to or above -30 °C (-22 °F) | 700 | January 1, 2026 |
kChillers (as a stand-alone product) | Comfort cooling | 700 | January 1, 2025 |
lChillers (as a stand-alone product) | Ice rinks | 700 | January 1, 2025 |
mData centers, computer room air conditioning, and information technology equipment cooling | Data centers, computer room air conditioning, and information technology equipment cooling | 700 | January 1, 2027 |
nIndustrial process refrigeration (not using chillers) | With refrigerant entering the evaporator below -50 °C (-58 °F) | Not covered | Not covered |
oIndustrial process refrigeration (not using chillers) | With refrigerant entering the evaporator equal to or above -50 °C (-58 °F) and less than -30 °C (-22 °F) | 700 | January 1, 2028 |
pIndustrial process refrigeration (not using chillers) | High temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F) | 300 | January 1, 2026 |
qIndustrial process refrigeration (not using chillers) | With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F) | 300 | January 1, 2026 |
rIndustrial process refrigeration (not using chillers) | With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F) | 150 | January 1, 2026 |
sRetail food - refrigeration stand-alone units | Retail food - refrigeration stand-alone units | 150 | January 1, 2025 |
tRetail food - refrigerated food processing and dispensing equipment | 500 g of refrigerant or less and outside scope of UL 621, edition 7 | 150 | January 1, 2027 |
uRetail food - refrigerated food processing and dispensing equipment | More than 500 g of refrigerant and outside scope of UL 621, edition 7 | R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12 | January 1, 2027 |
vRetail food - refrigerated food processing and dispensing equipment | Ice cream makers within the scope of UL 621, edition 7 | R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12 | January 1, 2028 |
wSelf-contained automatic commercial ice machines | Batch type: harvest rate <=1,000 lb ice per 24 hours | 150 | January 1, 2026 |
xSelf-contained automatic commercial ice machines | Continuous type: harvest rate <=1,200 lb ice per 24 hours | 150 | January 1, 2026 |
ySelf-contained automatic commercial ice machines | Batch type: harvest rate above 1,000 lb ice per 24 hours | R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12 | January 1, 2027 |
zaSelf-contained automatic commercial ice machines | Continuous type: harvest rate above 1,200 lb ice per 24 hours | R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12 | January 1, 2027 |
zbCold storage warehouses | With 200 or more lb refrigerant charge, excluding high temperature side of cascade system | 150 | January 1, 2026 |
zcCold storage warehouses | With less than 200 lb refrigerant charge | 300 | January 1, 2026 |
zdCold storage warehouses | High temperature side of cascade system | 300 | January 1, 2026 |
zeRefrigerated transport4 | Intermodal containers with refrigerant temperature entering the evaporator below -50 °C (-58 °F) | Not covered | Not covered |
zfRefrigerated transport4 | Intermodal containers with refrigerant temperature entering the evaporator equal to or above -50 °C (-58 °F) | 700 | January 1, 2025 |
zgRefrigerated transport4 | Road—self-contained products | R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5 | January 1, 2025 |
zhRefrigerated transport4 | Marine—self-contained products | R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5 | January 1, 2025 |
Refrigeration, Air Conditioning, and Heat Pumps – Restricted Systems by Sector and Subsector Table*
Sort by
Subsector | System | Global Warming Potential Limit or Prohibited Substances | Installation Compliance Date5 |
---|---|---|---|
aStationary residential and light commercial air conditioning and heat pumps |
Residential and light commercial air conditioning and heat pump systems (e.g., mini-splits, unitary systems) |
700 | January 1, 20256 |
bStationary air conditioning and heat pumps | Variable refrigerant flow systems | 700 | January 1, 2026 |
cChillers | Industrial process refrigeration with exiting fluid below -50 °C (-58 °F) | Not covered | Not covered |
dChillers | Industrial process refrigeration with exiting fluid from -50 °C (-58 °F) to -30 °C (-22 °F) | 700 | January 1, 2028 |
eChillers | Industrial process refrigeration with exiting fluid above -30 °C (-22 °F) | 700 | January 1, 2026 |
fChillers | Comfort cooling | 700 | January 1, 2025 |
gIce rinks | Ice rinks | 700 | January 1, 2025 |
hData centers, computer room air conditioning, and information technology equipment cooling | Data centers, computer room air conditioning, and information technology equipment cooling | 700 | January 1, 2027 |
iIndustrial process refrigeration (not using chillers) | With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F) | 150 | January 1, 2026 |
jIndustrial process refrigeration (not using chillers) | With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F) | 300 | January 1, 2026 |
kIndustrial process refrigeration (not using chillers) | High temperature side of cascade systems and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F) | 300 | January 1, 2026 |
lIndustrial process refrigeration (not using chillers) | Temperature of the refrigerant entering the evaporator from -50 °C (-58 °F) to -30 °C (-22 °F) | 700 | January 1, 2028 |
mIndustrial process refrigeration (not using chillers) | Temperature of the refrigerant entering the evaporator below -50 °C (-58 °F) | Not covered | Not covered |
nCold storage warehouses | With 200 or more lb refrigerant charge, excluding high temperature side of cascade system | 150 | January 1, 2026 |
oCold storage warehouses | With less than 200 lb refrigerant charge | 300 | January 1, 2026 |
pCold storage warehouses | High temperature side of cascade system | 300 | January 1, 2026 |
qRetail food - supermarkets | With 200 or more lb refrigerant charge, excluding high temperature side of cascade system | 150 | January 1, 2027 |
rRetail food - supermarkets | With less than 200 lb refrigerant charge | 300 | January 1, 2027 |
sRetail food - supermarkets | High temperature side of cascade systems | 300 | January 1, 2027 |
tRetail food - remote condensing units | With 200 or more lb refrigerant charge, excluding high temperature side of cascade system | 150 | January 1, 2026 |
uRetail food - remote condensing units | With less than 200 lb refrigerant charge | 300 | January 1, 2026 |
vRetail food - remote condensing units | High temperature side of cascade system | 300 | January 1, 2026 |
wRetail food - remote refrigerated food processing and dispensing equipment | Retail food - remote refrigerated food processing and dispensing equipment | R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12 | January 1, 2027 |
xRemote automatic commercial ice machines | Remote automatic commercial ice machines | R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5 | January 1, 2027 |
yRefrigerated transport | Intermodal containers with exiting fluid temperature from a chiller below -50 °C (-58 °F) | Not covered | Not covered |
zaRefrigerated transport | Intermodal containers with exiting fluid temperature from a chiller equal to or above -50 °C (-58 °F) | 700 | January 1, 2025 |
zbRefrigerated transport | Road systems | R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5 | January 1, 2025 |
zcRefrigerated transport | Marine systems | R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5 | January 1, 2025 |
*These tables are for informational purposes only and should not be relied on for compliance purposes. Please refer to 40 CFR Part 84, Subpart B for full details.
1. Sale, distribution, and export of these products is prohibited three years after the manufacture and import compliance date.
2. See regulatory text for specific types of aerosol products subject to the later compliance date. Excludes metered dose inhalers using HFC-134a or HFC-227ea or defense sprays using HFC-134a as a propellant.
3. Includes blown foam, products incorporating blown foam, and pre-blended polyol products. Excludes composite structural preformed polyurethane foam for trailer use and for marine use.
4. New products only; does not apply to equipment that is operational during transport.
5. EPA is restricting the installation of new field-assembled systems. Components used to repair existing systems are not subject to these restrictions.
6. New systems with a GWP above 700 can be installed until January 1, 2026, so long as all components are manufactured or imported prior to January 1, 2025 (refer to the Interim Final Rule for additional details).