Trumbull Energy Center
1. Facility Information
Trumbull Energy Center
2. Location
3. Distance from US/Canada Border
144 km to Rondea Park near Erie Beach near Chatham-Kent, Ontario
4. Facility Type and Size
940-megawatt natural gas-fired combined cycle gas turbine (CCGT) electric generating facility
5. Sources of Emissions
The facility consists of two combined cycle combustion turbines (3,025 mmBtu/hr heat input turbine at ISO conditions and 237 mmBtu/hr heat input duct burner) with dry low NOx combustors, selective catalytic reduction (SCR), and catalytic oxidizer, a 37.8 mmBtu/hr natural gas fired auxiliary boiler with low-NOx burners and flue gas recirculation, a 1,140 kW (mechanical) emergency diesel-fired generator, a 300 hp emergency diesel-fired fire pump, and a 10-cell wet cooling tower equipped with a high efficiency drift eliminator.
6. Type of Fuel
Natural gas for the turbines and boiler and diesel fuel for the emergency generator and fire pump.
7. Type and Quantity of Emissions
Pollutant | Tons/Yr |
---|---|
CO |
275.1 |
NOx |
240.5 |
PM10 |
135.2 |
PM2.5 |
131.6 |
SO2 |
42.1 |
VOC |
101.4 |
H2SO4 | 31.5 |
GHGs expressed as CO2e | 3,371,414 |
NH3 | 198.0 |
Pb | 1.4 E-03 |
8. Emission Control Technology
The combined cycle combustion turbines will be equipped with dry low NOx combustors, selective catalytic reduction (SCR), and catalytic oxidation. The auxiliary boiler will be equipped with low-NOx burners and flue gas recirculation. The wet cooling tower will be equipped with a high efficiency drift eliminator.
9. Date Permit Application Received
The permit application associated with this permit was received on 12/11/2019. Note that this permit will replace the permit issued on that expired; the associated permit application was received on 2/16/2017.
10. Stack Height and Diameter
Turbine Stack #1: vertical unobstructed, 170 ft high, 21 ft diameter
Turbine Stack #2: vertical unobstructed, 170 ft high, 21 ft diameter
Auxiliary Boiler Stack: vertical unobstructed, 170 ft high, 2.5 ft diameter
Emergency Generator Stack: vertical unobstructed, 12.6 ft high, 0.83 ft diameter
Fire Pump Stack: vertical unobstructed, 13.5 ft high, 0.5 ft diameter
10 Cooling Tower Cell Stacks (each): vertical unobstructed, 43.5 ft high, 35.6 ft diameter